Precision cooling||Datacenter cooling|Data Center cooling|Telecom cooling

AIRSYS Precision cooling

Home > Product > Telecom Cooling
  1. MOBILECOOL-SPLIT Telecommunication Base Station Special Temperature Control Unit
  2. MOBILECOOL-SPLIT Telecommunication Base Station Special Temperature Control Unit

MOBILECOOL-SPLIT Telecommunication Base Station Special Temperature Control Unit

Brief IntroductionMOBILECOOL-SPLIT is a split type telecommunication base station special air conditioner that meets requirements in aspects of high efficiency & energy saving, various power supplies,

Top

information

Brief Introduction
MOBILECOOL-SPLIT is a split type telecommunication base station special air conditioner that meets requirements in aspects of high efficiency & energy saving, various power supplies, environment friendly refrigerants, various installation conditions, extensive working scope and product safety, etc. By integrating numerous advantages and latest technologies of current telecom air conditioners, the unit may provide the values exceeding expectations for the user. MOBILECOOL-SPLIT includes indoor and outdoor unit. All the components are assembled at factory and parameters are set.
Capacity
5.5~14.9kW  
Applications
Various telecommunication base stations
Advanced technology electronic devices switching room
Power distribution station
Industrial process control center
Features
Energy-saving operating
Built-in free cooling system, operating when the outdoor temperature is lower than the room temperature. Reducing the cooling of compressor, the unit can greatly reduce the energy consumption. When the indoor and outdoor temperature difference reaches 10°C, the free cooling may provide the cooling capacity equal to or even greater than such capacity provided by the mechanical cooling. The maximum energy saving quantity per year can reach 90%;


Lower & front air supply mode
With the lower & front air supply mode, the cooling capacity provided by the air conditioner may cool the equipment within the shelter more effectively, reducing the operation time of unit and its cooling energy consumption;


Easy maintenance
The main components can be accessed and maintained in front of the unit, The panel is light, weight of each panel less than 10kg.


Strong structure
The structure is strong enough to be able to transport on low grade ways.


Dual cooling source
Equipped with both mechanical cooling system and free cooling system as standard. The fresh air free cooling is designed to be the primary source of cooling.
 

The frames and panels of the unit are made from galvanized steel plate and coated with anti-corrosion protection coating.

 

High sensible heat ratio:above 0.85.

Wide working range(-30°C~53°C)

 

Working mode auto-alternated
The unit automatically selects mechanic cooling or free cooling according to the indoor and outdoor temperature. When power outage or mechanical cooling failure appears, the unit will be alternated to free cooling mode.
 

Balance all units working time automatically
 

Comfort mode
Service engineer can choose the HVAC work with comfort mode (22℃,adjustable) by pressing 2 buttons on the user terminals.
Half an hour later, the unit will recover to work at normal temperature.

 

Except for a large number of necessary alarms, fire/smoke alarm, power inverter box power failure alarm, prime power outage alarm are also be provided;
 

Humidity control
 

Random restart when power recovered, step-test
 

Running data logging
 

Data output
Standard RS485 communication card enable automatic download of logs. The format of the data should be CSV or Excel file.

 

Model

 

5R1D1

7R1D1

10E1D2

13E1D2

15E1D2

Supply air scheme

 

O:Up flow; DL: Replacement

Power source

 

220V-1Ph-50Hz

380V-3Ph-50Hz

Cooling capacity(1)

kW

5.5

7.6

10.4

13.3

14.9

Free cooling capacity(2)

kW

5.9

5.9

7.4

11.6

11.6

Compressor

 

Hermetic Rotary Type

Hermetic Scroll Type

Supply fan

Type

 

AC Centrifugal Fan

Air volume

m3/h

1800

1800

2250

3500

3500

Width*Depth*Height

mm

600*500*1700

600*500*1700

750*500*1700

750*500*1700

750*500*1700

Weight

kg

70

80

150

160

165

Condenser unit

Model

 

CMD3

CMD4

CMD4

CMD5

CMD6

Width*Depth*Height

mm

808*509*789

808*509*789

808*509*789

1004*509*930

1250*509*930

Weight

kg

29

35

35

43

92

(1) Return air dry bulb temperature 27℃, RH50%,Outdoor dry bulb temperature35℃;
(2) Indoor temperature and outdoor temperature difference (ΔT) is 10℃(only for DL air supply scheme unit).