Precision cooling||Datacenter cooling|Data Center cooling|Telecom cooling

AIRSYS Precision cooling

Home > Product > Telecom Cooling

    METROCOOL

    Top

    information

    Brief Introduction
    METROCOOL unit is specially designed for industry environment, standing up to high temperature, heavy pollution and continuous working demand and offering high efficiency, strict fire proofing, various power supplies and widely working condition with high reliability. METROCOOL is a split air conditioning unit with rational structure for convenient maintenance.
    Capacity
    5.2~13.0 kW  
    Applications
    Rail transit
    Mine workings
    Metallurgy industry
    Petrochemical industry
    Industrial process control center
    Features
    High reliability

    High temperature resistance

    Corrosion-proof

    Fire-proof

    Good structure design and easy maintenance

    Options
    Electric heating elements

    Special condenser

    Communication protocol conversion card

    Various power source
    As customer requirement, the below power sources are
    available.
    230/1/50
    208~230/1/60
    415/3/50
    208~230/3/60
    460/3/60

    Liquid injection cooling device

    Communication Card

    Wall mounting kits

     

     

    Model

     

    MTC.5

    MTC.7

    MTC.10

    MTC.13

    MTC.5

    MTC.7

    MTC.10

    MTC.13

    MTC.5

    MTC.7

    MTC.10

    MTC.13

    Power source

     

    380V-3Ph-50Hz

    220V-1Ph-50Hz

    208~230V-1Ph-60Hz

    Cooling capacity(1)

    kW

    5.2

    7.3

    10.0

    13.0

    5.2

    7.3

    10.0

    13.0

    5.0

    6.8

    10.7

    13.0

    Unit max. operating power input

    kW

    3.2

    3.9

    5.3

    6.5

    3.4

    4.0

    5.5

    6.5

    2.9

    3.8

    5.3

    6.8

    Unit max. operating current

    A

    8.0

    9.5

    12.2

    16.5

    14.7

    18.9

    27.0

    24.6

    13.1

    16.6

    24.8

    31.2

    Indoor unit

     

     

     

     

     

     

     

     

     

     

     

     

     

    Fan type

     

    Double Inlet Centrifugal Fan

    Double inlet  Centrifugal Fan

    Double inlet  Centrifugal Fan

    Air volume

    m3/h

    1400

    1400

    1600

    2000

    1400

    1400

    1600

    2000

    1400

    1400

    1600

    2000

    Width*Depth*Height

    mm

    1295*280*680

    1295*310*870

    1295*280*680

    1295*310*870

    1295*280*680

    1295*310*870

    Weight

    Kg

    52

    54

    64

    67

    52

    54

    64

    67

    52

    54

    64

    67

    Outdoor unit

     

     

     

     

     

     

     

     

     

     

     

     

     

    Compressor

     

    Hermetic scroll type

    Hermetic scroll type

    Hermetic scroll type

    Fan type

     

    Axial flow fan

    Axial flow fan

    Axial flow fan

    Width*Depth*Height

    mm

    1260*590*880

    1440*590*1125

    1305*590*1500

    1260*590*880

    1440*590*1125

    1305*590*1500

    1260*590*880

    1440*590*1125

    1305*590*1500

    Weight

    Kg

    91

    95

    123

    145

    91

    95

    123

    145

    91

    95

    123

    145

    Piping connection

     

     

     

     

     

     

     

     

     

     

     

     

     

    Condensing water drainage

    mm

    16

    16

    16

    16

    16

    16

    16

    16

    16

    16

    16

    16

    Refrigerant liquid

    in

    3/8

    1/2

    1/2

    1/2

    1/2

    1/2

    1/2

    1/2

    1/2

    1/2

    1/2

    1/2

    Refrigerant gas

    in

    1/2

    5/8

    3/4

    3/4

    5/8

    5/8

    3/4

    3/4

    5/8

    5/8

    3/4

    3/4

    (1) Top grade air flow, return air dry bulb temperature 27℃,wet bulb temperature 19℃,outdoor dry bulb temperature35℃, wet bulb temperature 24℃.