AIR-SYS REFRIGERATION ENGINEERING
THE EXPERT FOR ICT COOLING
AIRSYS >> ENGLISH >> Air conditioners for Critical Applications

Air-conditioners for Critical Applications, which are installed in Hi-tech facilities, telephone
exchangers, telecommunication, data center, control center, test center, Internet and so on
to keep room temperature and relative humidity as well as air purity within very close limits.
--------------------------------------------------------------------------------------------------
Type Cooling capacity

Cooling Capacity:7100kW
--------------------------------------------------------------------------------------------------
Features:
   Greater air volume with less air enthalpy difference and higher sensible capacity leads to energy saving
 Work normally under wide weather conditions: -3050
 Scroll type full-hermetic compressor
 More reliable with two independent refrigerant system in one unit (E2 version)
 Condenser fans (S4 above) are speed stepless controlled according to compressor discharge pressure
 Immersed electrode humidifier provides clean humidifying with automatic washing cycle ensuring higher  efficiency
and increased system life.
 Advanced microprocessor control system provides complete unit management and protection, and support  group control
as well as remote control.
 Silence operation
 Flexible enough to suit various installation situations
 Fresh air system is optional
--------------------------------------------------------------------------------------------------
Physical Data
DXA Series(air-cooled)
Model
7.E1
10.E1
15.E1
15.E1
22.E1
24.E1
36.E1
40.E1
24.E2
36.E2
40.E2
40.E2
52.E2
74.E2
88.E2
Type
S0
S0
S1
S3
S4
S5
S6
S7
S5
S6
S7
S8
S9
S9
S10
Cooling capacity
Entering air at 24 with 50% and outdoor air at 32
R22-Total(KW)
7.4
9.4
15.5
17.0
22.3
26.0
36.9
41.9
26.0
36.9
41.9
44.8
59.6
78.5
93.5
R22-Sensible(KW)
7.1
9.0
15.0
16.1
20.6
24.3
34.2
38.5
24.3
34.2
38.5
43.2
55.8
72.3
88.2
Capacity Steps
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
Electric heating(KW)
2.55
2.55
5.1
9
9
9
13.5
13.5
9
13.5
13.5
13.5
18
18
18
Humidifier Capacity(kg/h)
4
4
4
4
4
4
8
8
4
8
8
13
13
13
13
Dimensions                              
Length(mm)
645
645
645
900
1105
1125
1360
1750
1125
1360
1750
2210
2680
2680
3415
Depth(mm)
410
410
645
860
840
860
860
860
860
860
860
860
860
860
900
Height(mm)
1820
1820
1930
1950
1930
1950
1950
1950
1950
1950
1950
1950
1950
1950
1950
Weight(kg)
150
155
205
288
300
390
445
605
375
450
610
710
1000
1050
1335
 
DXW Series(water-cooled)
Model
15.E1
22.E1
24.E1
36.E1
40.E1
24.E2
36.E2
40.E2
40.E2
52.E2
74.E2
88.E2
Type
S3
S4
S5
S6
S7
S5
S6
S7
S8
S9
S9
S10
Cooling capacity
Entering air at 24 with 50% and outdoor air at 32
R22-Total(KW)
17.6
24.6
27.2
37.9
43.8
27.2
37.9
43.8
47.7
61.8
81.0
98.4
R22-Sensible(KW)
16.6
23.4
24.8
34.6
40.3
24.8
34.6
40.3
44.5
56.8
74.1
92.8
Capacity Steps
1
1
1
1
1
2
2
2
2
2
2
2
Electric heating(KW)
9
9
9
13.5
13.5
9
13.5
13.5
13.5
18
18
18
Humidifier Capacity(kg/h)
4
4
4
8
8
4
8
8
13
13
13
13
Dimensions                        
Length(mm)
900
1105
1125
1360
1750
1125
1360
1750
2210
2680
2680
3415
Depth(mm)
860
840
860
860
860
860
860
860
860
860
860
900
Height(mm)
1950
1930
1950
1950
1950
1950
1950
1950
1950
1950
1950
1950
Weight(kg)
288
330
405
455
625
375
450
650
650
1000
1000
1415
 

CW Series(Chilled water)

Type
S2
S3
S4
S5
S6
S7
S8
S9
S10
Cooling capacity                  
R22-Total(KW)
16.4
21.2
24.8
26.0
34.1
44.2
57.9
71.3
100.0
R22-Sensible(KW)
13.3
19.2
23.2
23.8
31.2
40.6
53.3
64.4
93.7
Electric heating(KW)
5.1
9
9
9
13.5
13.5
13.5
18
18
Dimensions                  
Length(mm)
755
900
1105
1125
1360
1750
2210
2680
3415
Depth(mm)
645
860
645
860
860
860
860
860
900
Height(mm)
1930
1950
1930
1950
1950
1950
1950
1950
1950
Weight(kg)
182
237
205
272
327
420
502
622
940